7.5
CVSSv2

CVE-2019-10919

Published: 14/05/2019 Updated: 04/01/2022
CVSS v2 Base Score: 7.5 | Impact Score: 6.4 | Exploitability Score: 10
CVSS v3 Base Score: 9.4 | Impact Score: 5.5 | Exploitability Score: 3.9
VMScore: 668
Vector: AV:N/AC:L/Au:N/C:P/I:P/A:P

Vulnerability Summary

A vulnerability has been identified in LOGO! 8 BM (incl. SIPLUS variants) (All versions < V8.3). Attackers with access to port 10005/tcp could perform device reconfigurations and obtain project files from the devices. The system manual recommends to protect access to this port. The security vulnerability could be exploited by an unauthenticated attacker with network access to port 10005/tcp. No user interaction is required to exploit this security vulnerability. The vulnerability impacts confidentiality, integrity, and availability of the device. At the time of advisory publication no public exploitation of this security vulnerability was known.

Vulnerability Trend

Vulnerable Product Search on Vulmon Subscribe to Product

siemens logo\\!8_bm_firmware

Exploits

Due to storing passwords in a recoverable format on Siemens LOGO! 8 PLCs, an attacker can gain access to configured passwords as cleartext ...

Mailing Lists

<!--X-Body-Begin--> <!--X-User-Header--> Full Disclosure mailing list archives <!--X-User-Header-End--> <!--X-TopPNI--> By Date By Thread </form> <!--X-TopPNI-End--> <!--X-MsgBody--> <!--X-Subject-Header-Begin--> [SYSS-2019-013]: Siemens LOGO! 8 - Missing Authentication for Critical Function (CWE-306) <!--X-Subject-Header-End--> ...