NA

CVE-2022-30312

Published: 07/09/2022 Updated: 16/09/2022
CVSS v3 Base Score: 6.5 | Impact Score: 3.6 | Exploitability Score: 2.8
VMScore: 0

Vulnerability Summary

The Trend Controls IC protocol through 2022-05-06 allows Cleartext Transmission of Sensitive Information. According to FSCT-2022-0050, there is a Trend Controls Inter-Controller (IC) protocol cleartext transmission of credentials issue. The affected components are characterized as: Inter-Controller (IC) protocol (57612/UDP). The potential impact is: Compromise of credentials. Several Trend Controls building automation controllers utilize the Inter-Controller (IC) protocol in for information exchange and automation purposes. This protocol offers authentication in the form of a 4-digit PIN in order to protect access to sensitive operations like strategy uploads and downloads as well as optional 0-30 character username and password protection for web page access protection. Both the PIN and usernames and passwords are transmitted in cleartext, allowing an attacker with passive interception capabilities to obtain these credentials. Credentials are transmitted in cleartext. An attacker who obtains Trend IC credentials can carry out sensitive engineering actions such as manipulating controller strategy or configuration settings. If the credentials in question are (re)used for other applications, their compromise could potentially facilitate lateral movement.

Vulnerability Trend

Vulnerable Product Search on Vulmon Subscribe to Product

honeywell trend_iq412_firmware

honeywell trend_iq411_firmware

honeywell trend_iq422_firmware

honeywell trend_iq4nc_firmware

honeywell trend_iq4e_firmware